Marshall Tufflex Products

Marshal Tufflex Overview

 

Marshall Tufflex Data Management Systems

 

STERLING TECHNICAL INFORMATION  

Sterling Twin Plus Technical Information

Sterling Twin Plus provides a fully integrated solution for the installation of high performance data and power cables in perimeter locations. The system has an extensive range of moulded fittings that incorporate a large 50mm bend radius control that is crucial to optimum cable performance. These fittings have also been designed to give improved appearance and security to surface cables. The twin segregated compartments and self aligning two-piece fittings, offer ease of access to each individual compartment for greater safety. Marshall-Tufflex Sterling Plus is an efficient economical solution to power and high performance data cable management.

POSITIONING
When using as a skirting system, sufficient clearance should be allowed for between the floor covering and the trunking (5mm + floor covering).

MATERIAL DATA ABS

Marshall-Tufflex Cable Management Products are produced in High Impact ABS grade material capable of withstanding the most hazardous conditions on site and which exceeds the most
stringent requirements of the British Standards.

Characteristics of Marshall-Tufflex High Impact ABS

Vicat Softening Point ISO 306

80ºC

Density

1.18g/cm3

Material

UL

UL listed

Flammability

UL94

V-1 at 1.5mm

V-0 at 2.00mm

Flammability

S4678:PT4:1982

Pass

Water Absorption

ASTM D570

0.3%

INSTALLATION

PVC-U: The Sterling Twin Plus base in PVC-U is supplied with pre-cut elongated holes at 250mm centres along its length to facilitate fastening. It should be secured at 500mm intervals and within 50mm of the end on each base section.

Aluminium: Sterling Twin Plus aluminium bases should be secured every 750mm utilising the grooves in the base to facilitate the drilling of 6mm clearance holes.

Internal couplers are not required on either PVC-U or aluminium base units.

When securing the base, use No. 8 round head screws and washers and avoid over-tightening to permit thermal movement. It is recommended that the use of plastic caps over screw heads to provide protection to the installed cables.

To cut the trunking base, use a fine-toothed saw or power tool. An electric variable angle jigsaw will also aid with the cutting to length and the 45-degree mitre.

JOINTS AND BENDS

At each joint, 3mm should be left for expansion. Internal bends must be mitred to ensure total enclosure of trunking. External bends should be cut square, flat bends must be mitred at 45 degrees, tees and crossovers are available pre-fabricated from the Sterling Twin Plus Range of fittings. None of the cutting is critical as the external moulded clip-on fittings have a built-in 7mm overlap for the lid and sidewalls to cover any inaccuracies.

SINGLE LENGTHS
Where it is required to fit a single length of trunking between two inside walls (under 3metres), it is advisable to place an additional coupler set in the centre of the trunking run in order to facilitate the removal of the cover if no accessory has been fitted.

MMT2/MMT4 ADAPTORS
Adaptors are available from the Sterling Twin Plus range of fittings. Two methods of fixing are as
follows:

1. drill a suitable hole in the sidewall of the Sterling Twin Plus base, thread cables through the hole and into the installed Mini Trunking. (Mini Trunking system technical information on page 220 of the main catalogue.)

2. cut the sidewall of the Sterling Twin Plus base to aid cable installation None of the cutting is critical as the clip-on fittings have a built-in overlap for the lid and sidewalls. (For the installation of the Mini Trunking accessory boxes, shrouded entry boxes, end caps and lid see page 220 in the main catalogue.)

BUSBAR ASSEMBLY

Upgrades the trunking to a 63A Busbar distribution system. Comprises: carrier support, carrier clip, Busbar rails, protective cover and cover screws. Can be fitted in either compartment of the base. Requires Busbar adaptor (EBS 60) to position the Busbar assembly within the trunking base (see page 209 in main catalogue). For Busbar fittings, accessories and installation please refer to relevant sections of the main catalogue.

ACCESSORY BOXES

Drill the main web if the accessory box is to be mounted in the alternative compartment to the supply. For boxes in the same compartment supply, remove the appropriate box knock-outs, feed the cable into box and then clip the box into trunking base. When assembled, the lid is butt joined to the edge of the box (ESSB1/2/3 only) which is subsequently covered when the accessory is fitted. When boxes are installed consecutively, a 14mm wide spacer (ES1) is required to cover the space between the boxes. All cut edges of lid are concealed by the accessory or external fitting.

LID AND FITTINGS

Install radius inserts according to instructions supplied with the individual fitting. When the cable installation is completed, start at a convenient point and snap-clip the lid and fitting alternately into place. Ensure the fitting overlaps the lid completely

DIMENSIONAL REFERENCE FOR OFFSETS AND TEES

The minimum double set that can be accommodated in the same plane (from internal to external bend).

STERLING TWIN PLUS CABLE CAPACITY

Type of Conductor

Size

Cable Factor

Max. No. Cables in A @ 45% Fill

Max No. Cables in B @ 45% Fill

Stranded PVC Power

1.5mm2

8.6

248

127

Stranded PVC Power

2.5mm2

12.6

100

86

Stranded PVC Power

4.0mm2

16.6

128

65

Stranded PVC Power

6.0mm2

21.2

100

51

Cat. 5e UTP

ø5.5mm*

30.2

70

36

Cat. 5e STP

ø6.0mm*

36

59

30

Cat. 6 UTP

ø6.5mm*

42.2

50

25

Cat. 6 STP

ø7.0mm*

49

43

22

*Typical values, check with manufacturer.

MINI 4 DATA

RADIUS CONTROL MINI FITTINGS

Radius Control Mini Fittings are designed to incorporate a large 50mm bend radius. This extensive range of stylish moulded fittings provides the exceptional data cabling control that is crucial to good performance in advanced LAN's and greatly improves security to surface data cables. Marshall-Tufflex Data Mini Fittings offer an efficient and economical solution to data cable management.

Two versions are available. The first offers complete control of the cable. The second, using the outer cover only, is aesthetically identical but does not offer the same level of cable control. Both versions can be used on new applications or, with small adaptations, to retrofit current installations.

INSTALLATION

Before installing the trunking, confirm the route of the main circuits, marking spurs and accessory box positions.

MOUNTING TRUNKING

Drill oversize holes and secure (at least every 375mm in low level applications) using No.8 round head screws. Do not over-tighten to allow thermal movement. (For thermal properties, see Material Data page) It is recommended that the use of plastic caps over screw heads to provide protection to the installed data cables.

JOINTS

At each joint, 3mm should be left for expansion. Internal bends must be mitred to ensure total enclosure of trunking.

External bends should be cut square with the corner.

At flat angles and tees, allowance should be made for the base moulding (assembly only) in the length of trunking base to be installed.

The cutting is not critical as the clip-on fittings have a built-in overlap for lids and sidewalls.

LID

When base and cable installation is completed, start at a convenient point and snap-clip the lid and fitting alternately into place. Ensure the fitting overlaps the lid completely.

(For the installation of Accessory boxes, Shrouded entry boxes, see page 220 in the main catalogue).

50mm radius internal 50mm radius 50mm radius 50mm radius

FLAPJACK RJ45 OUTLETS

SURFACE MOUNTING PLATE

OVERALL DIMENSIONS:

          1G Faceplate (1 & 2 port) 

86 x 86 x 8mm

          2G Faceplate (4 port) 

86 x 146 x 8mm

Material 

ABS, PC, V0 rated

Colour 

White/RAL 9010

Cut-out size 

37 x 22.5mm

OUTLET CONNECTION MODULE CAT. 5e/6 UNSHIELDED AND SHIELDED

The Cat. 5e/6 connection module complies with the latest international standard proposals, including full interoperability and backwards compatibility.

MAIN FEATURES

  • Complies with the latest Cat. 5e/6 standard proposals of ISO/IEC.

  • Conforms to Cat. 6 requirements according to EIA/TIA.

  • Compatible with Cat. 6 standard plugs

  • Tool-free connection technique for solid and stranded data cables with wire sizes AWG 22-24.

  • Pair sequencing and re-useable IDC contacts.

  • Simple and time-saving shield contacting with integral strain relief.

  • Halogen-free material.

MECHANICAL DATA

Material 

Polycarbonate (UL94V-0)

Mating cycles 

>1000

Wire diameter 

AWG 24 – AWG 22

Insulation diameter 

0.8-1.6mm

Wire strain relief 

Through clamps in IDC block

Cable strain relief 

Through cable ties

Shield contacting 

Shield lance

Earthing 

2 earthing terminals for plugs

Shield material 

CuSn, tin-plated, 2-4um

ELECTRIC AND TRANSMISSION DATA

Contact resistance 

<50mOhm (cond-cond)

Contact resistance 

<20mOhm (shield-shield)

Insulation resistance 

<500Mohm (500 VDC)

Dielectric strength 

1000Veff (cond-cond)

Dielectric strength 

1500Veff (cond-shield)

Coupling resistance 

IEC 96-1

1 MHz 

<15mOhm

10 MHz 

<100 mOhm