| Model |
5
|
7.5
|
10
|
15
|
20
|
| Apparent power (kVA) |
5
|
7.5
|
10
|
15
|
20
|
| Active power (kVA) |
4
|
6
|
8
|
12
|
16
|
| AC input (mains) |
| Number of phases |
3
|
| Voltage |
323 to 444 V
|
| Frequency (Hz) |
47 to 63
|
| AC ouput (load) |
| Number of phases |
1
|
| Voltage |
220/230/240 V
|
Frequency (Hz)
synchron with mains |
50 / 60 ± 1 %
|
| General |
Battery backup time
on full load (mn) |
8
|
10
|
10
|
10
|
10
|
| Efficiency (%) |
91
|
92
|
92
|
93
|
93
|
| Overload capacity |
50 % for 10 sec, 30 % for 1 min
|
| Crest factor |
up to 5:1
|
| Output distortion (%) |
<4
|
<4
|
<4
|
<4
|
<4
|
| Noise level (dBA) |
45
|
46
|
46
|
50
|
50
|
| Operating temperature |
0 to 40 ° C(1), 40 ° C for up to 8 hours, 35 ° C for up to 24 hours
|
| Dimensions and weight |
| Height (mm) |
730
|
910
|
910
|
1085
|
1085
|
| Width (mm) |
360
|
400
|
400
|
560
|
560
|
| Depth (mm) |
420
|
550
|
550
|
680
|
680
|
| Net weight (kg) |
81
|
176
|
206
|
370
|
450
|
| Gross weight (kg) |
94
|
191
|
221
|
418
|
478
|
Key:
(1) ideal battery running conditions require temperatures between 15 ° C and 25 ° C.
For temperatures in excess of 25 ° C, battery life is halved for each additional 10 ° C.
|