Rated power (Pn) in kVA
(power factor 0.8) |
20 |
30 |
40 |
50 |
60 |
80 |
100 |
120 |
160 |
200 |
|
UPS input (mains 1) |
|
Voltages |
380 V - 10% (option - 15%) to 415 V + 15 % 3-phase
On request: 208 V, 220 V and 480 V |
|
Frequency |
50 or 60 Hz +/- 10% |
|
Power factor |
0.95 with filter |
|
Distortion |
THDI < 4% with THM filtering |
|
Bypass input (mains 2) |
|
Voltages |
380, 400 or 415 V +/- 10 % 3-phase + neutral
On request: 208, 280 or 480 V |
|
Frequency |
50 or 60 Hz +/- 10% |
|
UPS output |
|
Steady-state voltages |
380, 400 or 415 V +/- 3%, 3-phase + neutral
On request: 208, 220 or 480 V |
|
Frequency |
50 or 60 Hz +/- 0.5 Hz |
|
Synchronisation range with bypass |
0.25 to 2 Hz in 0.25 Hz steps |
|
Voltage transients (dynamic performance) |
+/- 2 % for load charge of
0 % to 100 % and 100 % to 0 % |
|
Permissible overload duration |
125% for 10 minutes, 150% for 1 minute |
|
Short-circuit current capacity without transfer to bypass |
Peak current > 2.33 In for 1 sec |
|
Distortion on linear loads at Pn |
THDU Ph/Ph <1.5%, Ph/N < 2% |
|
Distortion on non-linear loads at Pn |
THDU Ph/Ph <2%, Ph/N < 3% |
|
Battery |
|
Back-up time |
8, 10, 15, 20, 30 and 60 min, other values on request |
|
Types |
Sealed lead acid (service life 5, 7 and 10 years), vented lead acid, Nickel Cadmium |
|
Voltage |
Floating: 423 to 463 V |
|
Voltage regulation |
Temperature correction |
|
Overall UPS efficiency at In |
|
Normal mode (%) |
92.5 |
93 |
92.5 |
92.5 |
92 |
93.5 |
93 |
92.5 |
92.5 |
92.5 |
|
Eco mode (%) |
95 |
97 |
97 |
97 |
97 |
97 |
97 |
97 |
97 |
97 |
|
Temperatures |
|
UPS Operation |
- 5° C to + 40° C, 40° C for 8 hours maximum |
|
Storage |
With battery: - 20° C to + 45° C,
Without battery : - 20° C to + 70° C |
|
Battery operation |
Optimum between + 15° C and + 25° C
The life of sealed is halved for each 10° C above this range |
|
General specifications |
|
Accoustic Noise (dBA) as defined by ISO 3746 |
58 |
58 |
58 |
60 |
60 |
62 |
64 |
65 |
67 |
68 |
|
Standards |
|
Design & performances |
IEC 146, ENV 50091-3 |
|
Safety |
EN 50091-1, IEC 60950 / EN 60950 |
|
EMC |
EN 50091-2, IEC 61000-2-2, IEC 61000-3-5, IEC 61000-4 |