Electrical characteristics

Rated power (Pn) in kVA
(power factor 0.8)

20

30

40

50

60

80

100

120

160

200

UPS input (mains 1)

Voltages

380 V - 10% (option - 15%) to 415 V + 15 % 3-phase
On request: 208 V, 220 V and 480 V

Frequency

50 or 60 Hz +/- 10%

Power factor

0.95 with filter

Distortion

THDI < 4% with THM filtering

Bypass input (mains 2)

Voltages

380, 400 or 415 V +/- 10 % 3-phase + neutral
On request: 208, 280 or 480 V

Frequency

50 or 60 Hz +/- 10%

UPS output

Steady-state voltages

380, 400 or 415 V +/- 3%, 3-phase + neutral
On request: 208, 220 or 480 V

Frequency

50 or 60 Hz +/- 0.5 Hz

Synchronisation range with bypass

0.25 to 2 Hz in 0.25 Hz steps

Voltage transients (dynamic performance)

+/- 2 % for load charge of
0 % to 100 % and 100 % to 0 %

Permissible overload duration

125% for 10 minutes, 150% for 1 minute

Short-circuit current capacity without transfer to bypass

Peak current > 2.33 In for 1 sec

Distortion on linear loads at Pn

THDU Ph/Ph <1.5%, Ph/N < 2%

Distortion on non-linear loads at Pn

THDU Ph/Ph <2%, Ph/N < 3%

Battery

Back-up time

8, 10, 15, 20, 30 and 60 min, other values on request

Types

Sealed lead acid (service life 5, 7 and 10 years), vented lead acid, Nickel Cadmium

Voltage

Floating: 423 to 463 V

Voltage regulation

Temperature correction

Overall UPS efficiency at In

Normal mode (%)

92.5

93

92.5

92.5

92

93.5

93

92.5

92.5

92.5

Eco mode (%)

95

97

97

97

97

97

97

97

97

97

Temperatures

UPS Operation

- 5° C to + 40° C, 40° C for 8 hours maximum

Storage

With battery: - 20° C to + 45° C,
Without battery : - 20° C to + 70° C

Battery operation

Optimum between + 15° C and + 25° C
The life of sealed is halved for each 10° C above this range

General specifications

Accoustic Noise (dBA) as defined by ISO 3746

58

58

58

60

60

62

64

65

67

68

Standards

Design & performances

IEC 146, ENV 50091-3

Safety

EN 50091-1, IEC 60950 / EN 60950

EMC

EN 50091-2, IEC 61000-2-2, IEC 61000-3-5, IEC 61000-4


Dimensions

Rated power (Pn) in kVA

20

30

40

50

60

80

100

120

160

200

UPS module dimensions and weights

Width (mm)

715

1 015

1 215

Depth (mm)

825

Heigth (mm)

1 400 / 1 900

1 900

Weight (kg)

450 / 500

490 / 540

800

1 200

Battery cabinet dimensions and weights (example for 10 min back-up time)

Height (mm)

1 400

Depth (mm)

825

Width (mm)

715

1 015

N/A

Weight (kg)

480

500

640

670

820

N/A

 

Height (mm)

1 900

Depth (mm)

825

Width (mm)

715

1 015

1 430

2 030

Weight (kg)

500

530

675

690

845

1 100

1 375

1 760

2 110

2 785