| Model |
SW20 |
SW30 |
SW45 |
SW60 |
SW90 |
SW120 |
| Per phase compensation capacity |
20 A rms |
30 A rms |
45 A rms |
60 A rms |
90 A rms |
120 A rms |
| Compensation capacity in the neutral (1) |
60 A rms |
90 A rms |
135 A rms |
190 A rms |
270 A rms |
360 A rms |
| AC supply input |
| Nominal voltage (2) |
400 V - 20 + 15% |
| Nominal frequency |
50 Hz, 60 Hz, ± 8% |
| Number of phases |
3 phases with or without neutral
(operation is possible on unbalanced or single phase loads) |
| Current transformers |
rating from 300/1 to 4000/1 |
| Technical specifications |
| Harmonic current compensated |
Orders 2 to 25, global compensation or specified harmonics |
| Rate of harmonic reduction |
THDI load/THDI network greater than 10 at nominal conditioner capacity |
| Current compensation of cosine phi |
Up to 1.0 |
| Response time |
< 40 ms |
| Overload |
Limitation to nominal current, continuous operation within these limits |
| Inrush current |
< twice nominal peak current |
| Losses |
1000 W |
1300 W |
2100 W |
2600 W |
4200 W |
5200 W |
| Noise level (ISO 3746) |
< 55dBA |
< 55dBA |
< 60dBA |
< 60dBA |
< 65dBA |
< 65dBA |
| Colour |
RAL 9002 |
| Environmental conditions |
| Operating temperature |
0 to 40°C continuous, < 25°C recommended |
| Relative humidity |
0 to 95% no condensing |
| Operating altitude |
< 1000 m |
| Reference standards |
| Construction and safety |
EN 50091-1 |
| Design |
IEC 146 |
| Protection |
IP 30 according to IEC 529 |
| Electromagnetic compatibility |
| Conducted and radiated emission |
En 55011 Class A |
| Immunity to electrostatic discharges |
IEC 1000-4-2 level 3 |
| Immunity to electromagnetic fields |
IEC 1000-4-3 level 3 |
| Immunity to impulse waves |
IEC 1000-4-4 and IEC 1000-4-5 levels 4 |
| Dimensions and weight |
W x H x D (mm)
(Inches) |
540 x 680 x 280
21.4 x 27 x 11.1 |
590 x 780 x 325
23.4 x 30.9 x 12.9 |
1180 x 780 x 325
46.8 x 30.9 x 12.9 |
Weight (kg)
(lbs) |
65
143 |
110
242 |
220
484 |