Pulsar CT Line Conditioners
Pulsar CT are time and money savers which will help you protect your company's sensitive electronic equipment (laboratory, process control...) against power fluctuations.
They monitor your power supply, avoid damage of the components of your electronic equipment. Pulsar CT guarantee service continuity that is vital for your business.
Unmatched Performances
- Input/Output Galvanic Isolation
- Permanent filtering
- Full short-circuit-proof
- Tight regulation
- Harmonic reduction
- Microbreak Protection (< 20 ms)
|
|
Ease of integration
- Compact
- Outstanding aesthetics
- USE or DIN Output Receptacles (CT 3/6/12)
- Front panel display
- Alarms (CT 30/50)
|
User interface and connections

Complete galvanic isolation Your power supply is permanently protected, even against a 4,000 volt transcient surge due to lightning! This kind of performances is the sign of a real high-end product.
Tight regulation and permanent filtering Whatever the voltage fluctuations you may get, Pulsar CT will permanently regulate the line within a 3 to 5 percent window.
This exceeds the performance of most voltage regulators in the market.
Utility line harmonic compensation Like Pulsar EX or SineWave for higher power ratings, Pulsar CT reduce harmonics regenerated on the utility by the load, enhancing the customer global power quality.
To ensure that nothing will stop you now, Pulsar CT come with a two-year warranty, the proof of a high level of reliability. With its outstanding aesthetics, Pulsar CT is the best series of today's Line Conditioners.
Tech Specs
| General |
| Power (VA/Watts) |
315/250 |
625/500 |
1250/1000 |
3000/2400 |
5000/4000 |
| Dimensions (H x W x D) |
253x172x400 |
253x172x400 |
253x172x400 |
293x300x500 |
293x300x500 |
| (mm / inches) |
10x6.8x15.8 |
10x6.8x15.8 |
10x6.8x15.8 |
11.6x12x20 |
11.6x12x20 |
| Weight (kg/lbs) |
10/22 |
15/33 |
25/55 |
40/88 |
51/112 |
| Input Connection |
1 cord + grounded plug |
Terminal block |
| Output Connection |
2 USE or DIN (model dependant) |
Terminal block |
| Input Voltage (Volts) |
230 V +/- 20 % |
| Frequency (Hz) |
50Hz |
| Output Voltage (Volts) |
230 Volts +/- 5 % (+/- 3 % for 230 Volts Input +/- 15 %) |
| Frequency (Hz) |
50Hz |
| THD |
< 3% at nominal linear load |
| Standards |
EMI EN 50 091 - 2 et 50 022/11 - B |
| Susceptibility |
EN 50 091 - 2 and IEC 1000 - 4 - 2 to 1000 - 4 - 5 |
| Safety |
CEI 950/EN 60 950/EN 50 091 - 1 |
| Environment |
| Response time |
30 ms |
| Temperature thresholds |
- 10° C, + 40° C |
| Warranty (country dependant) |
2 years |
|