» How to build a CLA configuration?
Pulsar EXtreme CLA
You need:
- 1 UPS without internal batteries or "0 minute" UPS module: Pulsar EXtreme 2000 or 3000
- "Install version" Module connection
- 1 CLA: Pulsar EXtreme CLA 2000 or 3000 VA
Comet EXtreme CLA 6 kVA
You need:
- 1 UPS "0 minute" UPS module: Comet EXtreme 6
- 1 CLA: Comet EXtreme CLA 6 kVA
Comet EXtreme CLA 12 kVA
You need:
- 1 UPS "0 minute" UPS module: Comet EXtreme 12
- 1 CLA: Comet EXtreme CLA 12 kVA
| TOWER |
UPS module
" 0 minute " |
CLA module |
Receptacle module |
| Pulsar EXtreme CLA 2000 VA configuration |
67744 |
67745 |
To be selected |
| Pulsar EXtreme CLA 3000 VA configuration |
67824 |
67825 |
To be selected |
| Comet EXtreme CLA 6 kVA configuration |
67880 or 67883 |
67886 |
Install module included |
| Comet EXtreme CLA 12 kVA configuration |
67920 or 67923 |
67926 |
Install module included |
| RACK |
UPS module
" 0 minute " |
CLA module |
Receptacle module |
| Pulsar EXtreme CLA 2000 VA configuration |
67764 |
67765 |
To be selected |
| Pulsar EXtreme CLA 3000 VA configuration |
67844 |
67845 |
To be selected |
| Comet EXtreme CLA 6 kVA configuration |
67893 |
67896 |
Install module included |
| Comet EXtreme CLA 12 kVA configuration |
67933 |
67936 |
Install module included |
» Installation specification (not supplied with CLA modules)
| |
Connection to the networks
|
Connection from the CLA
to the batterie cabinet
|
CLA 2000 VA
CLA 3000 VA
CLA 6 kVA |
- 1 cable of 2.5 mm2
- 1 circuit-breaker 10A C curve |
- 1 armed cable of 4 mm2
(6 m maximum length)
- 1 circuit-breaker 25A B curve |
| CLA 12 kVA |
- 2 cable of 2.5 mm2
- 2 circuit-breaker 10A C curve |
- 1 armed cable of 4 mm2
(6 m maximum length)
- 1 circuit-breaker 50A B curve |
|